The BDS Series Blowdown Separators are designed to safely separate hot water and the flash steam generated from boilers during blowdown. The vessel is designed to equalize to atmospheric pressure for disposal of the flash and hot water. Stainless steel strike plate and internal steel baffles direct the flow cyclonically for efficient separation. Optional aftercooler packages with temperature regulator available to temper condensate prior to discharge in municipal sewer
Model BDS
Inlet Sizes 3/4", 1", 1-1/2", 2", 2-1/2"
Connections 150# RF
Body Material Carbon Steel
PMO Max. Operating Pressure 150 PSIG
TMO Max. Operating Temperature 366ºF
PMA Max. Allowable Pressure 150 PSIG @ 562˚F
How It Works:

Dimensions (mm):

Flow rate lookup table: