IB Dump Steam Trap

IB bucket steam traps are used to discharge condensate for saturated steam systems. Commonly used on main pipes, heaters.

 

Advantages:

- Less affected by water hammer. 

- The discharge hole is located above the steam trap so it is less affected by dirt. 

- Special stainless steel structure inside. 

- Maintenance when the steam trap is still installed on the pipeline. 

- Integrated filter, one-way valve, bottom discharge.

Model 1031, 1032, 1033, 1034,
           1041, 1042, 1044, 1038S
Sizes 1/2”, 3/4”, 1”, 11/4”, 11/2”
Connections NPT
Body Material Cast Iron
Options Internal check valve, Thermic vent
PMO Max. Operating Pressure 250 PSIG
TMO Max. Operating Temperature 450ºF
PMA Max. Allowable Pressure 250 PSIG up to 450ºF
TMA Max. Allowable Temperature 450ºF @ 250 PSIG

 

How It Works:

When the trap is filled with condensate, the inverted bucket inside the steam trap loses its buoyancy and rests on the bottom of the trap. This pulls the disc off the seat allowing condensate to be discharged through the seat orifice located at the top of the trap. When steam enters, it fills the inverted bucket causing the bucket to float to the surface which closes the discharge valve, containing the steam in the system. Eventually, the steam is bled off through a small hole in the top of the bucket causing it to sink, which repeats the cycle.

 

Dimensions (mm):

 

              

 

 

SIZE & WEIGHT_ inches
Model A B C D Weight
(lbs)
1031 3.75 5.875 5 2.75 5
1031S* 3.75 5.875 5 2.75 5
1032 3.75 6.875 5 4.25 6
1033 5.625 9.06 6.5 5.375 15
1034 7 11.75 7.75 7.03 27
1041 3.75 6.06 5 3.43 5
1042* 3.75 7.06 5 4.43 6
1044* 7 12.375 7.125 7.375 30
1038S* 7 12.375 7.125 7.375 30
*With Integral Strainer  

 

   With filter:

Size Model Code PMO Weight Cross Ref.
NPT PSI lbs Armstrong
1/2” IB1041-12-N-20 20 7 880
3/4” IB1041-13-N-20
1/2” IB1041-12-N-80 80 7 880
3/4” IB1041-13-N-80
1/2” IB1041-12-N-125 125 7 880
3/4” IB1041-13-N-125
1/2” IB1041-12-N-150 150 7 880
3/4” IB1041-13-N-150
1/2” IB1042-12-N-15 15 8 881
3/4” IB1042-13-N-15
1/2” IB1042-12-N-30 30 8 881
3/4” IB1042-13-N-30
1/2” IB1042-12-N-70 70 8 881
3/4” IB1042-13-N-70
1/2” IB1042-12-N-125 125 8 881
3/4” IB1042-13-N-125
1/2” IB1042-12-N-200 200 8 881
3/4” IB1042-13-N-200
1/2” IB1042-12-N-250 250 8 881
3/4” IB1042-13-N-250
3/4” IB1044-13-N-15 15 37 883
1” IB1044-14-N-15
3/4” IB1044-13-N-30 30 37 883
1” IB1044-14-N-30
3/4” IB1044-13-N-60 60 37 883
1” IB1044-14-N-60
3/4” IB1044-13-N-80 80 37 883
1” IB1044-14-N-80
3/4” IB1044-13-N-125 125 37 883
1” IB1044-14-N-125
3/4” IB1044-13-N-180 180 37 883
1” IB1044-14-N-180
3/4” IB1044-13-N-250 250 37 883
1” IB1044-14-N-250
11/4” IB1038S-15-N-15 15 37 883
11/2” IB1038S-16-N-15
11/4” IB1038S-15-N-30 30 37 883
11/2” IB1038S-16-N-30
11/4” IB1038S-15-N-60 60 37 883
11/2” IB1038S-16-N-60
11/4” IB1038S-15-N-80 80 37 883
11/2” IB1038S-16-N-80
11/4” IB1038S-15-N-125 125 37 883
11/2” IB1038S-16-N-125
11/4” IB1038S-15-N-180 180 37 883
11/2” IB1038S-16-N-180
11/4” IB1038S-15-N-250 250 37 883
11/2” IB1038S-16-N-250

 

No filter:

Size Model Code PMO Weight Cross Ref.
NPT PSI lbs Armstrong
1/2” IB1031-12-N-20 20 7 800
3/4” IB1031-13-N-20
1/2” IB1031-12-N-80 80 7 800
3/4” IB1031-13-N-80
1/2” IB1031-12-N-125 125 7 800
3/4” IB1031-13-N-125
1/2” IB1031-12-N-150 150 7 800
3/4” IB1031-13-N-150
1/2” IB1032-12-N-15 15 8 811
3/4” IB1032-13-N-15
1” IB1032-14-N-15
1/2” IB1032-12-N-30 30 8 811
3/4” IB1032-13-N-30
1” IB1032-14-N-30
1/2” IB1032-12-N-70 70 8 811
3/4” IB1032-13-N-70
1” IB1032-14-N-70
1/2” IB1032-12-N-125 125 8 811
3/4” IB1032-13-N-125
1” IB1032-14-N-125
1/2” IB1032-12-N-200 200 8 811
3/4” IB1032-13-N-200
1” IB1032-14-N-200
1/2” IB1032-12-N-250 250 8 811
3/4” IB1032-13-N-250
1” IB1032-14-N-250
1/2” IB1033-12-N-15 15 17 812
3/4” IB1033-13-N-15
1/2” IB1033-12-N-30 30 17 812
3/4” IB1033-13-N-30
1/2” IB1033-12-N-70 70 17 812
3/4” IB1033-13-N-70
1/2” IB1033-12-N-125 125 17 812
3/4” IB1033-13-N-125
1/2” IB1033-12-N-200 200 17 812
3/4” IB1033-13-N-200
1/2” IB1033-12-N-250 250 17 812
3/4” IB1033-13-N-250
3/4” IB1034-13-N-15 15 30 813
1” IB1034-14-N-15
3/4” IB1034-13-N-30 30 30 813
1” IB1034-14-N-30
3/4” IB1034-13-N-60 60 30 813
1” IB1034-14-N-60
3/4” IB1034-13-N-80 80 30 813
1” IB1034-14-N-80
3/4” IB1034-13-N-125 125 30 813
1” IB1034-14-N-125
3/4” IB1034-13-N-180 180 30 813
1” IB1034-14-N-180
3/4” IB1034-13-N-250 250 30 813
1” IB1034-14-N-250

 

 

 

Flow Rate Table:

 

 

Combined application with Blowdown Valves:

 

 

Combined application with Check Valves:

 

 

TL Plus Engineering specializes in providing comprehensive solutions for saturated steam systems, covering everything from heating system calculations and piping and valve selection—tailored to specific temperature and pressure control applications—to ensuring safe and efficient system operation. The company also develops solutions to calculate and minimize energy losses in saturated steam systems.

Application of the Watson McDaniel IB Inverted Bucket Steam Trap for Saturated Steam Systems.

 

TL Plus Engineering serves as the exclusive distributor and developer for Watson McDaniel’s US-manufactured valve product lines in the Vietnamese market.